簡易檢索 / 詳目顯示

研究生: 蕭珮芳
Hsiao, Pei-Fang
論文名稱: 液流阻尼器在高科技廠房的減震應用
Aseismatic Application of Fluid Dampers on High Tech. Fab. Structures
指導教授: 徐德修
Hsu, Deh-Shiu
學位類別: 碩士
Master
系所名稱: 工學院 - 土木工程學系
Department of Civil Engineering
論文出版年: 2005
畢業學年度: 93
語文別: 中文
論文頁數: 76
中文關鍵詞: 結構控制液流阻尼器耐震設計高科技廠房軟弱層
外文關鍵詞: structure control, fluid damper, aseismatic design, high-tech factory buildings, weak story
相關次數: 點閱:146下載:3
分享至:
查詢本校圖書館目錄 查詢臺灣博碩士論文知識加值系統 勘誤回報
  •   本文針對實際的高科技廠房,加以配置液流阻尼器來進行防震措施之研究。在地小人稠的台灣,因實際空間運用之需求,高科技廠房結構已由只有一層軟弱層,增加為兩層或多層軟弱層。該樓層相對於其他樓層來說,對地震之抵抗能力較其他正常層相差甚遠。

      藉由有限元素分析軟體ETABS 8.08版,建立一個六樓結構模型,其第一、四樓層為軟弱層,針對此具軟弱層之特殊結構,除分析其動力行為外,並提出以液流阻尼器進行補強防震之構想,試以諸多不同補強策略進行分析,互相比對其防震功能。分析結果顯示,適當之防震補強措施,無論在位移和加速度,均能發揮控制效果,達到增加結構耐震能力的目的。

      The high tech fab which has relatively weaker stories is designed and built in order to afford enough space for the needs of the line of the production. Only external columns are designed in such stories with relatively very big spans. Consequently, the resistance to earthquake is relatively small for those weaker floors when compared to other floors which are normally designed with inner columns.

      By means of numerical analysis with ETABS 8.08 software package, a six-story structure model is established with the first and fourth stories designed to be weak floors mentioned above. In addition to the dynamic analysis, various policies for aseismatic purposes by using fluid dampers are investigated and analyzed to this model structure. Results show the proper aseismatic measures do provide positive control purpose in the aspects of variables such as displacement and acceleration to this model structure with weak stories.

    中文摘要 Ι 英文摘要 Ⅱ 致謝 Ⅲ 目錄 Ⅳ 表目錄 Ⅴ 圖目錄 Ⅶ 第一章 緒 論 1-1 前言 1 1-2 消能裝置 3 1-3 研究動機 5 1-4 研究方向 6 1-5 本文內容架構 7 第二章 文獻回顧與理論分析 2-1 液流阻尼器的簡介 8 2-2 阻尼器的基本理論 11 2-3 結構之動力分析基礎理論 16 第三章 高科技廠房結構個案說明 3-1 高科技廠房的模型建立 20 3-2 高科技廠房的結構分析檢驗 29 3-3 阻尼器的安裝 32 3-4 結構體地震歷時 37 第四章 分析結果 4-1 選擇節點及桿件圖 38 4-2 未加裝液流阻尼器之原結構反應 41 4-3 針對不同軟弱層配置不同液流阻尼器 43 4-4 配置液流阻尼器在原結構的不同位置 59 第五章 結論與建議 5-1 結論 70 5-2 建議 71 參考文獻 72

    1. 董倫道, 王彥博, “新城斷層對竹科之影響與對策”, 高科技廠房震害防治研討會論文集, 民國九十二年十二月。
    2. Tsai, C. S., Chen, K. C. and Chen, C. S. (1998),“Seismic Resistibility of High-Rise Buildings with Combined Velocity-Dependent and Velocity -Independent Devices ”ASME/JSME PVP Conference, San Diego, California, U.S.A., Vol. 366, July, 103-110
    3. A. S. WHITTAKER, M. C. CONSTANTINOU, and C. A. KIRCHER (1996), “Seismic Rehabilitation Using Supplemental Damping Systems”,
    11th World Conference on Earthquake Engineering, , pp. 219.226.
    4. 卜君平,“高樓之主動控制研究”, 國立成功大學土木工程研究所博士論文, 民國七十六年十一月。
    5. 徐國榮, “三層樓房屋主動控制之震動台試驗”, 私立淡江大學土木工程研究所碩士論文, 民國九十年六月。
    6. Yao-J.T.P. (1972),“Concept of structural control”, Journal of the Structrual Division, ASCE, Vol. 98, NO. ST7, pp. 1567.1574.
    7. 蔡森淵、葉俊雄譯,“現代自動控制工程”, 上冊, 民國七十六年十月,復漢出版社。
    8. Constantionu, M. C. and Symans, M. D. (1992),“Experimental and analytical Investigation of seismic of structures with supplemental fluid viscous dampers”Report No.NCEER-92-0032, National Center for Earthquake Engineering Research, SUNY at buffalo, New York.
    9. Soong, T. T. and Constantionu, M. C. (1994), “Passive and Active Structural Vibration Control in Civil Engineering”, Springer-Verlag, New York.
    10. Tsopelas, P., Okamoto, S., Constantinou, M. C., Ozaki, D., and Fujii, S. (1994), “Experimental and Analytical Study of Systems Consisting of Sliding Bearings, Rubber Restoring Force Devices, and Fluid Dampers”, Published as Report NCEER-94-0002, by the National Center for Earthquake Engineering Research, State University of New York at Buffalo.
    11. Reinhorn, A. M., Li, C., and Constantinou, M. C. (1995), “experimental and Analytical Investigation of Seismic Retrofit of structures with Supplemental Damping, Part 1 - Fluid Viscous Damping Devices”, Published as Report NCEER-95-0001, by the National Center or Earthquake Engineering Research, State University of New York at Buffalo.
    12. 盧思源﹐”矽液對液流阻尼器效能影響之研究”﹐國立成功大學土木工程研究所碩士論文﹐民國八十九年六月。
    13. 王冠凱, “液流阻尼器全尺寸結構防振功能之振動台測試”, 國立成功大學土木工程研究所碩士論文, 民國九十一年六月。
    14. 粘克銘, “液流阻尼器在軟弱層的應用”, 國立成功大學土木工程研究所論文, 民國九十二年六月。
    15. 徐德修, 李永峰, 許伯銓, 周尚儀, 楊欣翰, (Jan.1999) “油壓阻尼器之研發及應用”, 財團法人中興工程顧問社專案研究報告,SEC/R-ST-99-06, 民國八十八年元月。
    16. 徐德修, 侯建元, 盧思源, 周尚儀, (Jan.2000) “高壓阻尼器之研發”, 財團法人中興工程顧問社專案研究報告, SEC/R-ST-01-01,民國八十九年元月。
    17. 徐德修, 侯建元, 李永峰, 郭吉生, (Apr.1999) “封閉式液流阻尼器結構減振之模型試驗”, 財團法人中興工程顧問社專案研究報告,SEC/R-ST-01-06, 民國九十年四月。
    18. 李永峰, “結構液流阻尼器之設計及應用”, 國立成功大學土木工程研究所碩士論文, 民國八十六年六月。
    19. 陳信元, “液流阻尼器物理特性之研究”, 國立成功大學土木工程研究所碩士論文, 民國九十年六月。
    20. 郭吉生, “液流阻尼器結構控制系統之模型試驗”, 國立成功大學土木工程研究所碩士論文, 民國九十年六月,
    21. 陳清泉, 蔡益超, 林超強, 鄒肇基, “高層建築物結構設計審查參考例研擬, 民國八十四年六月。
    22. Taylor, D. P. (1996), “Fluid Dampers for Applications of Seismic Energy Dissipation and Seismic Isolation”, Eleventh Word Conference on Earthquake Engineering, No. 798.
    23. Ahmadi, H, R, and Muhr, A. H. (1993),“Prediction of Performance of Base Isolation Systems Utilizing High Damping Natural Rubber”Proceedings of the ASME Pressure Vessels and Piping Conference, CO,USA, Vol. 256, 121-125.
    24. Skinner, R. I., Kelly, J. M. and Heine, A. J. (1975), “Hysteresis Dampers for Earthquake-Resistant Structure”
    Earthquake Engineering and Structural Dynamics, Vol.3,287-296.

    下載圖示 校內:立即公開
    校外:2005-01-14公開
    QR CODE