簡易檢索 / 詳目顯示

研究生: 羅啟文
Lo, Chi-Wen
論文名稱: 高火載廠房建築之火場延燒與火害結構安全
Fire spread and structural fire safety for the steel industrial building with high fire load densities
指導教授: 賴啟銘
Lai, Chi-Ming
學位類別: 碩士
Master
系所名稱: 工學院 - 土木工程學系
Department of Civil Engineering
論文出版年: 2014
畢業學年度: 102
語文別: 中文
論文頁數: 80
中文關鍵詞: 火災輕鋼構FDS有限元素防火安全
外文關鍵詞: Fire, Light-steel structure, FDS, FEM, Fire safety
相關次數: 點閱:108下載:0
分享至:
查詢本校圖書館目錄 查詢臺灣博碩士論文知識加值系統 勘誤回報
  • 近年來,輕鋼構建築在房屋設計上逐漸被廣泛應用,雖然具成本低、工時短等特性,在耐震上更具有其優越性,唯獨在高溫環境下,其材料強度會大幅減弱,因此有必要對其火場行為進行了解。
    本文目的為利用數值模擬軟體探討廠房建築於高火載量時之火災行為,所有梁柱構件參數採用國內常見之SN490B鋼材與歐洲Eurocode之建議值。本文首先用FDS火災模擬軟體做實尺寸火場重建, 以求得模擬結果之溫度歷時。接著再利用有限元素軟體ANSYS進行耦合分析,參考CNS12514防火試驗法做性能上之評估。
    由模擬結果可知,位於高火載量空間時,將使火災得以迅速擴大,燃燒所產生之高溫熱能與煙,持續蓄積於空間高處,使屋頂之梁柱系統產生嚴重變形,若此時消防人員破門而入控制火勢,外部空氣之灌入卻會使火勢加劇,讓火場溫度升高,廠房內大量的濃煙不僅阻礙視線,高溫更使屋頂板產生崩塌,造成廠內人員嚴重傷亡。

    The purpose of this study is to investigate the behavior for industrial building with high fire loading density with computer numerical simulation software. In the beginning, the fire simulation software “FDS” was used to rebuild a model to simulate the scene of a fire. And then, based on the evaluation of CNS12514 fire test method, the transient thermal analysis in finite element method (FEM) model is performed by entering the predicted temperatures profiles with ANSYS software. The result shows that the fire will rapidly expand in a high fire load space. High-temperature heat and smoke generated from continuously burn will accumulate in top of space and made the roof severely deformed. When the firefighters broke into the fire scene to control the fire, the outside air will be drew into the space and exacerbate the fire. A large amount of smoke and high temperature will also make the roof collapse and cause more serious injury even death.

    中文摘要I Extended AbstractII 誌謝XI 目錄XII 表目錄XIV 圖目錄XV 第一章 緒論1 1.1 背景與目的2 1.2 文獻回顧3 1.3 論文架構5 第二章 研究方法6 2.1 火災模擬6 2.1.1 對象空間與模擬情境7 2.1.2 FDS軟體介紹19 2.1.3 火源設計26 2.1.4 網格靈敏度分析28 2.2 有限元素分析30 2.2.1 ANSYS軟體介紹30 2.2.2 熱分析30 2.2.3 非線性結構分析34 2.2.4 高溫狀態下鋼結構之材料性質38 第三章 結果與討論46 3.1 基本觀察47 3.2 火源規模之影響56 3.3 火源位置之影響57 3.4 開口部面積之影響61 3.5 屋頂型式之影響63 3.6 小結68 第四章 結論與建議74 4.1 結論74 4.2 建議75 參考文獻76

    Bailey, C.G, and Toh, W.S, “Behaviour of concrete floor slabs at ambient and elevated temperatures”, Fire safety Journal, Vol.42, pp.425-436,2007.

    Chow ,W.K. “One the ‘Cabin’ Fire Safety Design Concept in the New Hong Kong Airport Terminal Buildings”, Journal of Fire Science, Vol.15, pp. 404-423,1997.

    Chen, C.J., Hsieh, W.D, Hu, W.C, Lai, C.M., Lin, T.H, “Experimental Investigation and Numerical Simulation of a Furnished Office Fire”, Buildingand Environment, Vol.45, pp.2735-42,2010.

    Duthinh, D., McGrattan, K., Khaskia, A. “Recent advances in fire-structure analysis”, Fire Safety Journal, Vol.43, pp.161-167, 2008.

    Eurocode 1, “Basis of Design and Actions on Structures-Part1.2:General Action-Actions on Structures Exposed to Fire”, (ENV1991-1-2), 1995.

    Eurocode 3, “Design of Steel Structures-Part1.2:General rules-Structural Fire Design”, (ENV1993-1-2), 1995.

    Eurocode 4, “Design of composite steel and concrete structures-Part1-2:General rules-Structural fire design”, (EN1994-1-2), 2005.

    Feasey, R.,and Buchanan, A.H. “Post-flashover Fires for Structural Design”, Fire Safety Journal, Vol. 37, pp.83–105,2002.

    Federal Emergency Management Agency, “World Trade Center Building Performance Study:Data Collection, Preliminary Observations, and Recommendations”, FEMA 403, May 2002.

    Forney, G.P., “User’s Guide for Smokeview Version 5- A Tool for Visualizing Fire Dynamics Simulation Data”, NIST, 2008.

    G.Ginda, W.Skowronski, “Elasto-Plastic Creep Behavior and Load Capacity of Steel Columns During Fire”, Journal of Constructional Steel Research, Vol.46, pp.312-313, 1998.

    Gillie M., “The Behaviour of Steel-Framed Composite Structures in Fire Conditions”, PhD thesis, University of Edinburgh, 2000.

    Iu, C. K., Chan, S. L., and Zha, X. X. “Nonlinear pre-fire and post-fire analysis of steel frames”, Engineering Structures, Vol. 27, pp. 1689-1702, 2005.

    Jowsey, A., Torero, J.L., Usmani, A., “Modelling of Structures in Fire:an Example of the Boundary Condition”, Proceedings of The International Technical Congress on Computational Simulation Fire Models in Engineering and Research, Santander (Spain), pp. 297-313, 2004.

    Kawagoe, K. “Fire Behavior in Rooms”, Building research Institute, Japan Report, No.27, 1958.

    Kwon,J., “Evaluation of FDS V.4:Upward Flame Spread”, Worcester Polytechnic Institute Press, MA, USA,2006.

    Liu, T.C.H., Fahad M.K., and Davies, J.M. “Experimental Investigation of Behaviour of Axially Restrained Steel Beam in Fire”, Journal of Contructional Steel Research, Vol.58, pp.1211-1230, 2002.

    Luecke WE, McCowan CN and Banovic SW, “Mechanical Propeties of Structural Steels”, Federal Building and Fire Safety Investigation of the World Trade Center Disaster, National institute of Standards and Technology, 2005.

    McGrattan, Kevin B., Baum, Howard R., Rehm, Ronald G., “Large Eddy simulations of Smoke Movement”, Fire Safety Journal, Vol.30 , pp. 161-178,1998.

    Ma, T.G, Quintiere, J.G, “Numerical Simulation of Axi-Symmetric Fire Plumes: Accuracy and Limitations”, Fire Safety Journal; Vol.38 pp.467-92, 2003.

    McGrattan, K., Klein, B., Hostikka, S., Floyd, J., “Fire Dynamics Simulator (Version 5) User’s Guide”, NIST, 2008.

    Wang Z., Jia F., Galea E.R., Patel M.K. and Ewer J., “Simulating one of the CIB W14 round robin test cases using the SMARTFIRE fire field model”, Fire Safety Journal, Vol.36 , pp. 661–667, 2001.

    Wickstrom, U., Duthinh, D., McGrattan, K., “Adiabatic surface temperature for calculating heat transfer to fire exposed structures”, Interflam 2007, London, England, September 3-5, pp.943, 2007.

    Wickstrom, U., “Adiabatic Surface Temperature and the Plate Thermometer for Calculating Heat Transfer and Controlling Fire Resistance Furnaces”, Fire Safety Science, Proceedings of the Ninth International Symposium, pp 1227-1238, 2009.

    Yin, Y.Z., and Wang, Y.C., “A Numerical Study of Large Deflection Behavior of Restrained Steel Beams at Elevated Temperatures”, Journal of Constructional Steel Research, Vol. 60, pp. 1029-1047, 2004.

    Yin, Y.Z., and Wang, Y.C., “Analysis of Catenary Action in Steel Beams Using a Simplified Hand Calculation Method, Part 1:Theory and Validation for Uniform Temperature Distribution”, Journal of Constructional Steel Research, Vol. 61, pp. 183-211, 2005.

    中國國家標準CNS總號12514,「建築物構造部分耐火試驗法」,經濟部中央標準局,2002。

    李鎮宏、蔡銘儒,「鋼結構梁柱組合火害行為數值分析與驗證研」,內政部建築研究所自行研究成果報告,2008。

    李鎮宏,「鋼構建築梁柱接頭火害行為之研究」,國立成功大學土木工程研究所,2012。

    林岳山華,「鋼結構梁柱接頭高溫反應之數值模擬」,國立成功大學土木工程研究所,2005。

    林子賓,「高溫下螺拴孔承壓能力之研究」,國立成功大學土木工程研究所,2006。

    林誠興,「建築物火災行為與結構安全之性能模擬分析」,行政院國家科學委員會專題研究計畫成果報告,2006。

    林誠興、王士承,「數值模擬技術應用於建築物火災情境重現之探討」,工業安全科技,pp46-53,2007。

    林振吉,「H型梁-箱型柱彎矩接頭之火害行為研究」,國立成功大學土木工程研究所,2008。

    林京蔚,「箱體式輕鋼構雙層框架之火害結構分析」,國立成功大學土木工程研究所,2010。

    「性能設計與設計火源驗證研究-防火性能設計之火源燃燒特性研究」,內政部建築研究所,2005。

    「建築防火安全設計與驗證研究」(以辦公室為例),內政部建築研究所,2005。

    「建築物構造防火性能驗證技術手冊」,內政部建築研究所,2009。

    許晉瑋,「鋼結構梁柱接頭在高溫環境下行為之數值模擬」,國立成功大學土木工程研究所,2007。

    莊有清,「鋼材在高溫環境下之行為探討」,國立成功大學土木工程研究所, 2004。

    莊英吉,「建築物防火區劃構件與部品之全尺寸火災試驗設備及方法開發」,國立台灣科技大學建築程研究所, 2007。

    黃義雄,「FDS預測ISO-9705房間試驗火場情境之可行性研究」,國立高雄第一科技大學環境與安全衛生工程所,2005。

    陳明宗,「複合式老舊住宅火災模擬分析以高雄縣民宅火災為例」,元智大學機械工程所,2008。

    趙隆瑞,「箱體式單元輕鋼構受火害高溫環境下行為研究」,國立成功大學土木工程研究所,2010。

    蔡宗奮,「單層多跨建築之火災與結構行為之數值模擬」,國立成功大學土木工程研究所,2010。

    無法下載圖示 校內:2016-07-01公開
    校外:不公開
    電子論文尚未授權公開,紙本請查館藏目錄
    QR CODE