電力電纜局部放電檢測與圖譜辨識之研究 Detection and Pattern Recognition for Partial Discharge in Power Cable |
| 指導教授: |
陳建富
Chen, Jiann-Fuh 梁從主 Liang, Tsorng-Juu |
| 學位類別: |
碩士 Master |
| 系所名稱: |
電機資訊學院 - 電機工程學系碩士在職專班 Department of Electrical Engineering (on the job class) |
| 論文出版年: | 2008 |
| 畢業學年度: | 96 |
| 語文別: | 中文 |
| 論文頁數: | 110 |
| 中文關鍵詞: | 交連聚乙烯電纜 、電力電纜終端接頭 、直路接續匣 、局部放電 |
| 外文關鍵詞: | Cross-linked polyethylene cable (XLPE), Cable joints cartridges, Partial discharge (PD), Power cable terminal |
| 相關次數: | 點閱:125 下載:0 |
| 分享至: |
| 查詢本校圖書館目錄 查詢臺灣博碩士論文知識加值系統 勘誤回報 |
電力電纜劣化原因有廠內製造、現場施工瑕疵、蟻害與老化等。本論文以25kV電力電纜為被試物,首先於高壓實驗室模擬常見之劣化現象,如電暈、刀傷及針孔空洞等,再進行局部放電圖譜檢測分析。同時進行現場電力電纜終端接頭、直路接續匣等局部放電圖譜檢測,與實驗室圖譜辨識資料比較分析。此外,文中以局部放電脈衝電流、暫態對地電壓與音射法檢測,顯示放電圖譜於電力電纜劣化推斷效果頗佳,可有效提升線上即時劣化判斷之準確性。
Deterioration of XLPE cable may be caused by the manufacturing process, site constructing, termite harm, and long time in service. In this study,25kV XLPE cable will corona, cut and scraped wound, punched wound.
Then, the partial discharge is measured and recorded. Further, the partial discharges of on-site cable heads and cable joints cartridges are measured and compared with laboratory experiments. They show that the partial discharge pulse current, transient earth voltages and acoustic emission method can provide feasible result for on-line deterioration diagnosis of XLPE cables.
[1]易經順,「模鑄型變壓器局部放電音射檢測系統之研製」,國立成功大學電機工程學系碩士論文,2001年5月。
[2]台灣電力股份有限公司,供電處供電單位變電設備維護手冊,2007年12月。
[3]台灣電力股份有限公司,區處設計手冊地下配電線路設計-電纜接頭,2000年。
[4]台灣電力股份有限公司,配電技術資料(二)地下配電器材,2000年。
[5]台電公司安南南濱線電纜驗收教育訓練,大亞電力電纜股份有限公司電力處研發部,2008年4月。
[6]經濟部,「屋外供電線路裝置規則」第11及第17條規定,2006年。
[7]經濟部,「屋內線路裝置規則」第七節第444條規定,2006年。
[8]台灣電力股份有限公司,「地下電纜測試準則完成報告」,2007年。
[9]莊坤山,台灣電力股份有限公司,電纜製程檢驗,2000年。
[10]儀測股份有限公司儀器研討會,The VLF 0,1 Hz Cosine Rectangular Wave Technology,2007年12月。
[11]賴政宏,「影像檢測技術於電氣設備不停電檢查之應用」,工安科技,2001年。
[12]台電公司供電處、業務處2001~2007年報資料統計。
[13]黃遠達,中國白蟻學概論,湖北科技學術出版社942頁,1999
年。
[14]鄭錦榮,「69kV栗林~矽三~矽品線事故現場勘查報告」,台電公司綜合研究所報告,2004年7月。
[15]陳錦生,環境用殺蟲藥之種類及使用,病媒防治專業技術人員訓練教材, 3-30頁,1999年。
[16]G. S. Eager, Jr., et al., “Effect of dc Testing Water Tree Deteriorated Cable and a Preliminary Evaluation of VLF as an Alternative,” IEEE Transactions on Power elivery, Vol. 7, No. 3, July 1992.
[17]IEC 60270 High-voltage test techniques-Partial discharge measurements,1999.
[18]N. H. Srinivas, et al., “Effect of & Testing on Aged XLPE Insulated Cables with Splices,” JICABLE 91, Paris, France, June 1991.
[19]陳建富,「模鑄型變壓器部分放電之音射檢測法」,行政院國家科學委員會電力科技產業學術合作研究計畫,1998年。
[20]Vallen-System GmbH, AE Testing Fundamentals Equipment Applications,HandBook, 2002.
[21]林德龍,「以小波理論為基礎之GIS局部放電檢測」,國立成功大學電機工程學系碩士論文,2006年6月。
[22]M. E. Haque, A. Darus, M. M. Yaacob and F. Ahmad, “Application of Acoustic Sensing and Signal Processing for PD Detection in GIS,” 1st International Conference on Information, Communications and Signal Processing, Singapore, pp.745-749, Sep, 1997.
[23]M. E. Haque , F. Ahmed , A. B. Darus and M. M. Yaacob, “Diagnosis of GIS Based on Acoustic Sensing Technique,” Proc. of International Conference on Advances in Power System Control, Operation and Management, IEE Hong Kong section, pp.556-558, Nov, 1997.
[24]A. Schei, S. Kyrkjecide, and V. Larsen, “Acoustic Insulation Analyzer for Periodic Condition Assessment of Gas Insulated Substations,"IEEE/PES Transmission and Distribution Conference and Exhibition,
pp.919-924, 2002
[25] P. P. Nelson and D. S. Glaster, “AE and Discrete Fracture Propagation in Rock”, Acoustic Emission / Microseismic Activity in Geological Structures and Materials, Proceedings of the 4th Conference,ed. By
Hardy H.R. Jr, pp.117-130,1989
[26]NDT Resource Center-Accoustic Properties for Metals in Solid Form http://www.ndt-ed.org/GeneralResources/MaterialProperties/UT/ut_matlprop_metals.htm,2008..
[27] American Society for Testing and Materials, ASTM, E976, Standard Guide for Determining the Reproducibility of Acoustic Emission Sensor Response1 and E610-82,1999.
[28] 電力電纜現場完工試驗說明會講義-局部放電雜訊識別檢測:智友光電公司,2006年03月。
[29] 戴政祺、謝如主、蘇經洲等,電力電纜絕緣狀態評估研究—電力電
纜局部放電之音射法檢測技術及系統開發,行政院國家科學委員會電力補助專案研究計畫,2008年。
[30]I. Shim, J. J. Soraghan, and W. H. Siew, “A Noise Reduction Technique for on-Line Detection and Location of Partial Discharges in High Voltage Cable Networks”, Measurement Science and Technology, pp.1708-1713, Nov. 2000.
校內:2038-08-21公開