研究生: 許家榮
Hsu, Chia-Jung
論文名稱: 降載下冷卻水塔之節水分析
Water Conservation Analysis for a Cooling Tower under Partial Load
指導教授: 邱政勳
Chiou, Jenq-Shing
學位類別: 碩士
Master
系所名稱: 工學院 - 機械工程學系碩士在職專班
Department of Mechanical Engineering (on the job class)
論文出版年: 2008
畢業學年度: 96
語文別: 中文
論文頁數: 55
中文關鍵詞: 排放冷卻水塔蒸發
外文關鍵詞: blow-down, cooling tower, evaporation
相關次數: 點閱:94下載:1
分享至:
查詢本校圖書館目錄 查詢臺灣博碩士論文知識加值系統 勘誤回報
  • 冷卻水塔是空調機及其他熱系統在排除大量廢熱時最有效益的方式,但冷卻水塔的運作往往耗用大量的水資源,這其中有許多非必要的耗水,尤其是當空調系統處於部分負載下。
    本文,利用一商業化的3噸冷卻水塔,並將一變頻控制器加裝在原本風扇馬達上,使其可隨著冷卻負載作變速的調整,在利用此可變轉速的冷卻水塔,建立一實驗迴路,來模擬一熱冷卻系統。
    文中之實驗測試主要是突顯出在部分負載下能夠省水及省電的程度。

    Evaporative cooling towers are among the most-efficient and cost-effective technologies for rejecting waste heat from air conditioning and otherthermal systems to the atmosphere. In the operation of cooling towers, however, they use significant volumes of water. In fact, the actual water consumption for a cooling tower is usually much more than it is necessary especially when it is operated under partial load.
    In this thesis, a commercialized 3-tons cooling tower was used to set up a test loop, which simulates an actual cooling system. A frequency-modulating control was added to the original fan motor such that the fan speed can be modulated according to the cooling load.
    The object of our tests in the study was focused on the actual conservation of water and electric energy under partial cooling load conditions.

    中文摘要 I 英文摘要 II 誌謝 III 目錄 IV 表目錄 VI 圖目錄 VII 符號說明 IX 第一章 緒論 1 1-1 前言 1 1-2 研究背景與動機 1 1-3 冷卻水塔的構造 2 1-4 冷卻水塔耗水途徑 5 1-5 文獻回顧 7 1-6 本文結構 9 第二章 冷卻水塔內之熱質傳遞 10 2-1 水與空氣的熱量與質量交換 10 2-2 冷卻水塔的性能與其他相關定義 15 2-2-1 冷卻水塔之NTU 15 2-2-2 冷卻水塔之冷卻水溫差及濕球接近度 17 2-2-3 冷卻水塔之操作線 18 2-3 蒸發損失 19 2-4 排放損失 23 2-4-1 水質劣化之成因 23 2-4-2 水質檢測方法 24 2-4-3 連續排放之耗水量估算 27 2-5 耗電量的減少 30 第三章 實驗設備與實驗方法 32 3-1 系統描述 32 3-2 實驗步驟 33 3-3 實驗注意事項 34 3-4 實驗設備 34 3-5 設備誤差 38 第四章 結果與討論 40 4-1 全載下的蒸發量、散熱量及耗電量 40 4-2 半載下降低冷卻水流量時的蒸發量、散熱量及耗電量42 4-3 半載下水量不變時的蒸發量、散熱量及耗電量 45 4-4 結果之討論 48 4-5 省電量之討論 51 第五章 結論與建言 52 5-1 綜合討論 52 5-2 未來展望 52 參考文獻 53

    [1] 李玲玲、楊育昌,臺灣水資源政策之探討,節約用水季刊第28
    期,2002年9月15日
    [2] 嘉南農田水利會96年度業務報告。
    [3] 王啟川,冷卻水塔的熱流設計,冷凍與空調2001年10月,pp.53-61
    [4] Mohiuddin & Kant, Knowledge base for the systematic design of wet cooling towers – Part II : Fill and other design parameters, Int. J. Refrig. Vol.19, No.1, pp.52-60, 1996
    [5] 黃錦文,冷卻水塔原理及計算,經濟部工業局八十六年度工業技
    術人才培訓計畫——冷卻水塔應用及節水技術
    [6] 竹科園區同業公會水電委員會
    [7] Daeil Aqua Co., Ltd., Tower Demand & Characteristic Curves,
    Cooling Tower Technical Site of Daeil Aqua Co., Ltd. for Cooling Tower Engineers, Operators and Purchasers, 2000-2001
    [8] Jaber.H and Webb.R.L, Design of Cooling Towers by the effective-NTU method,ASME Journal of Heat and Mass Transfer111,pp837-843,1989
    [9] Klopper & Kroger, Cooling Tower Performance Evaluation:Merkel,Poppe,and e-NTU Methods of Analysis, Journal of Engineering for Turbines and Power.Vol.127,pp1-7,2005
    [10] Fisenko & Brin,Simulation of a Cross-flow Tower Performance,International Journal of Heat and Mass Transfer 50,pp. 3216-3223,2007
    [11] You & Tseng & Guo, A case study on the wastewater reclamation
    and reuse in the semiconductor industry, Resources, Conservation and Recycling 32, pp.73-81, 2001
    [12] Alawi & Alhajji & Reda, The effect of soft tap water chemistry on fatigue crack growth of steel, Engineering Fracture Mechanics Vol. 53, No. 3, pp.387-398, 1996
    [13] http://www.corrosion-doctors.org/NaturalWaters/Puckorius.h
    tm
    [14] Lu & Wong & Stoff, Exergetic analysis of cooling systems with
    ozonation water treatment, Energy Convers. Mgmt Vol.39, No.14, pp.1407-1422, 1998
    [15] Daeil Aqua Co., Ltd., Fan Efficiencies, Cooling Tower Technical Site of Daeil Aqua Co., Ltd. for Cooling Tower Engineers,Operators and Purchasers, 2000-2001
    [16] ALAJAN,SMIAI & ELANI,Effective Tools Toward Electrical Energy Conservation in Saudi Arabia, Energy Convers.Mgmt. Vol39, No.13, pp.1337-1349,1998
    [17] Mohiuddin & Kant, Knowledge base for the systematic design of wet cooling towers - Part I : Selection and tower characteristics, Int. J. Refrig. Vol.19, No.1, pp.43-51, 1996
    [18] Lemouari & Boumaza,Thermal Performance Investigation of a Wet Cooling Tower,Applied Thermal Engineering 27,pp.902-909,2007
    [19] http://www.corrosion-doctors.org/NaturalWaters/Ryznar.htm
    [20] Daeil Aqua Co., Ltd., Energy Saving Methods, Cooling Tower
    Technical Site of Daeil Aqua Co., Ltd. for Cooling Tower Engineers, Operators and Purchasers, 2000-2001
    [21] 個人諮詢:台灣省自來水公司第七區管理處
    [22] http://www.corrosion-doctors.org/NaturalWaters/Langelier.h
    tm
    [23] 成功大學碩士論文,謝博丞,2004
    [24] Hawlader & Liu, Numerical study of the thermal-hydraulic
    performance of evaporative natural draft cooling towers,
    Applied Thermal Engineering 22, pp.41-59, 2002
    [25] 黃錦文、蔡瑞益、張永鵬,冷卻水塔之熱力計算方法(上),冷
    凍與空調2001年10月,pp.85-94
    [26] CYT soft Psychrometric Chart,Version 2.15
    [27] 經濟部標準檢驗局,水量計檢定檢查技術規範,編號:CNMV49,版
    次:第三版
    [28] 經濟部標準檢驗局,電度表檢定檢查技術規範,編號:CNMV46,版
    次:第二版

    下載圖示 校內:立即公開
    校外:2008-08-13公開
    QR CODE